Aykom Air Dryers 1200 M3H
Product Description:
HK series air driers are designed under the principle of “Maximum performance under tough conditions” and operate from 60°C inlets to 50°C ambient temperature using environmentally-friendly R134a gas and wide ablation area condensers.
Advantages
- Integrated filter
- Compact design
- Easy access to the cooling circuit
- Interior ventilation
- Exterior ventilation ducts
- Automatic discharge system
- Insulation to prevent external heat and keep the performance at the top level
- Independent power panel
- Easy electrical connection of the drier
- Hot Gas Bypass Valve
Specifications:
MODEL TYPE: TMP1200 | |
Capacity | 20 |
Dimensions WxLxH (mm) | 950x730x1370 |
Gross Weight (kg) | 230 |
Choosing a Dryer
Please refer to the below when choosing a dryer.
For example, if an air compressor delivers 100m3/h at 7 bars and the dryer inlet temperature is 45°C and ambient temperature is 35°C.
Debit/Flow Rate x F1 x F2 x F3 100 x 1 x 1.18 x 1.14 = 134,52m2
Ambient Temperature:
Ambient Temperature | 25 ˚C | 30˚C | 35˚C | 40˚C | 45˚C |
Coefficient | 1,00 | 1,07 | 1,14 | 1,22 | 1,35 |
Inlet Temperature:
Inlet temperature of dryer | 25 ˚C | 30˚C | 35˚C | 45˚C | 50˚C | 60˚C |
Coefficient | 0,70 | 0,85 | 1 | 1,18 | 1,67 | 2,1 |
Working Pressure:
Working pressure (bar) | 4 | 6 | 7 | 8 | 10 | 12 | 13 |
Coefficient | 1,25 | 1,06 | 1 | 0,96 | 0,9 | 0,86 | 0,84 |